Peak flow is higher than Capacity #

Reason
- The calculated sewage flow rate is higher than the volumetric capacity.
Solution
- Double check the PE value at the pipe (to avoid duplicated PE values/ overdesign results)
- Adjust pipe diameter to bigger size
- Iterate sewer diameter from “No” to “Yes”
Gradient is out of range #

Reason
- Gradient inserted is not within range specified in the Project Settings. (Default limit: 1/200 < 1/x < 1/50)
Solution
- Input gradient to be within range that is defined in the Project Settings.
- Set the gradient iteration from “No” to “Yes”
- If required, use the Constraint Parameters function to adjust the gradient limit.
Velocity is out of range #

Reason
- Velocity of sewage is not within range specified in the Project Settings (Default limit: 0.4m/s < x < 4.0m/s)
Solution
- Adjust pipe diameter/ Set the diameter iteration from “No” to “Yes”
- Adjust gradient/ Set the gradient iteration from “No” to “Yes”
- If required, use the Constraint Parameters to customize the velocity limit